Serviço Rápido para Substituição Total de Peças HMI
casa / tudo / Allen Bradley /

Panelview 600

Panelview 600

  • Series overview
  • More information
  • Select by specs
  • Troubleshooting
  • Brand New In StockShips Today

    12 Months VICPAS Warranty

    Urgent Worldwide Shipping

    The Allen Bradley PanelView Standard 600 Operator Interface Terminals have a 5 inch color flat-panel with 10 Function Keys. Use the function keys on keypad terminals to initiate functions on the terminaldisplay. These keys may have custom legends. On the keypad & touch screen terminals, you can initiate functions by using the function keys and/or touch screen objects. VIPCAS supply PanelView 600 Terminals touchscreen and membrane keypad for repair. All of them are brand new and support 365 Days VICPAS Warranty.
    The most complete Allen Bradley HMI Parts Center

  • In Stock
    • Suppy Touchscreen, Keyboard, LCD Display, and Plastic Case for Allen Bredley Panelview 600 Replacement

    • Touch screen Technology: analog resistive

    • Display Description: Color Active Matrix Thin Film Transistor (TFT)

    • Application Memory: 190 K Application Runtime; 240 K Flash (application objects + text + bitmaps)

    • Keypad Description: Stainless steel domed membrane

    • Communication Ports: EtherNet/IP, DeviceNet, ControlNet, DH+, Remote I/O, DH-485, RS-232 (DH-485), RS-232 (DF1)

    • Operating Temperature: 0…55° C (32…131° F)

    • Non-Operating Temperature: -25…70° C (-13…158° F)


  • How to Install the Allen Bradley PanelView 600 in a Panel?


    1. Cut an opening in the panel by using the panel cutout template provided with the terminal and remove any sharp edges or burrs.

    2. Make sure the terminal sealing gasket is properly positioned on the terminal, particularly around the mounting studs as shown. This gasket forms a compression type seal. Do not use sealing compounds.

    3. Place the terminal in the panel cutout.

    4. Install the 4 mounting clips (2 on top, 2 on bottom). The ends of the clips slide into the slots on the terminal.

    5. Tighten the clip mounting screws by hand until the gasket seal contacts the mounting surface uniformly.

    6. Alternately tighten the self-locking nuts or mounting clip screws until the terminal is held firmly against the panel.

    7. Tighten the nuts or screws to a torque of 1.13 Nm (10 lb-in).

    8. Remove protective installation labels over top vents of terminal.

procurar:
modeloDescrição当前库存
Você quer saber rapidamente a cotação do produto que você precisa?
  • Citação Rápida
  • Envio para todo o planeta
  • 12 meses de garantia
  • Serviço Personalizado
subscrição
CLASSIFICAÇÃO
MANTENHA CONTATO
Por favor, envie sua mensagem para nós
*Email
Tel
*Título
*Contéudo
Upload
  • Suporta apenas .rar/.zip/.jpg/.png/.gif/.doc/.xls/.pdf, máximo de 20M
CONTATE-NOS
Código QR
Web para celular